The control you assign must use an analog tag with a Floating
Point data type. If you use Device tags (for DH+, ControlNet
Unscheduled, or Modbus), the tag must specify a floating-point
address in the programmable controller. If you use ControlNet
Scheduled tags, the tag must specify floating point in the data
type. If you use RIO, the tag must be configured with a Block
Transfer File address. For more information see Chapter 6,
Defining Tags, in the PanelBuilder 1400e Configuration Software
for Windows User Manual
.

Note: If you use the Implicit option, the application will be
compatible only with PanelView Firmware Version 2 or later. The
application will not be compatible with earlier versions.

Fixed Position specifies that a decimal point always appears in a
fixed position, and a fixed number of digits is always displayed
after the decimal point. You can specify the number of digits to
follow the decimal point.

The number of digits after the decimal determines the minimum
number of digits in the value to be sent to the control. For
example, if the setting was for three digits after the decimal, an
operator’s entry would appear as follows:

Digits Entered

Number Displayed

Keypad Numeric Input Value
(to PLC)

БББББББ

БББББББ

1

БББББББ

БББББББ

.1

ББББББББ

ББББББББ

100

БББББББ

БББББББ

12

БББББББ

БББББББ

.12

ББББББББ

ББББББББ

120

БББББББ

БББББББ

123

БББББББ

БББББББ

.123

ББББББББ

ББББББББ

123

БББББББ

БББББББ

1234

БББББББ

БББББББ

1.234

ББББББББ

ББББББББ

1234

БББББББ

БББББББ

12345

БББББББ

БББББББ

12.345

ББББББББ

ББББББББ

12345

Note: Although you can configure up to 15 digits after the
decimal point, 10 or more digits may generate a Mistake message
on the PanelView terminal. PanelView converts the decimal
number into a signed long value, with a range of –2,147,483,648
to 2,147,483,647. If the converted number is outside this range,
the Mistake message appears.

If the setting was for 15 digits after the decimal, an operator’s
entry would appear as follows:

Digits Entered

Number Displayed

Keypad Numeric Input Value
(to PLC)

0000000000000015

0.000000000000015

15

БББББББ

БББББББ

0100000000000015

БББББББ

БББББББ

0.100000000000015

ББББББББ

ББББББББ

ERROR
(100000000000015)

"

"