Install or replace the logic module – Rockwell Automation 2711PC-xxxx PanelView Plus 6 Compact Terminals User Manual User Manual

Page 108

Advertising
background image

108

Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014

Chapter 5

Install and Replace Components

Install or Replace the Logic
Module

The display modules and logic modules for the 1000 terminals can be ordered as
separate components for field installation. If modules are ordered as separate
components, attach the logic module to the display module before panel
installation.

1. Disconnect power from the terminal.
2. Set the display module display-side down on a clean, flat, stable surface.
3. Position the logic module over the back of the display module, aligning the

logic module connector with the connectors on the display module.

4. Push down on the logic module until it is firmly seated.
5. Tighten the four captive screws that secure the logic module to the display

module and torque to 0.58 N•m (5…7 lb•in).

Before replacing a logic module, you must first remove the communication
module, if attached.

Follow these steps to replace a logic module.

1. Disconnect power from the terminal.
2. Disconnect all power and communication cables.

3. Set the display module display-side down on a clean, flat, stable surface.

WARNING: Do not connect or disconnect any communication cable
with power applied to this device or any device on a network. An
electrical arc could cause an explosion in hazardous location
installations. Be sure power is removed or the area is known to be
nonhazardous before proceeding.

Captive

Screw