Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014

127

Connections and Communication

Chapter 6

Use only hi-speed USB 2.0 certified cables for error-free transmissions.

Connect only externally-powered USB hubs to the terminal. Before attaching
devices to a USB hub, make sure the power adapter is connected and powered on.

Ethernet Connection

The Ethernet port connects to a controller on an EtherNet/IP network by using
standard Ethernet and network connections. The port also supports application
transfers and printing.

Ethernet Connector

The Ethernet port has an RJ45, 10/100Base-T connector for network
communication and supports MDI/MDI-X connections.

WARNING: USB devices not powered by the USB port must be within the same
enclosure as the terminal. USB devices must be connected to a ground system
common with the terminal or used with a USB hub providing galvanic isolation.

TIP

The 2711P-RN20 Ethernet communication module is available for the
1000 terminals if another Ethernet port is required. The module has its own
unique IP address.

Table 41 - Ethernet Connector Pinout

Connector

Pin

Pin Name

Pin

Pin Name

RJ45 Connector

1

Transmit +

5

Unused

2

Transmit –

6

Receive –

3

Receive +

7

Unused

4

Unused

8

Unused

Table 42 - Ethernet Status Indicators

Indicator

Color

Description

Link Integrity

Yellow

On when a link is present.