Rockwell Automation 2711PC-xxxx PanelView Plus 6 Compact Terminals User Manual User Manual

Page 120

Advertising
background image

120

Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014

Chapter 5

Install and Replace Components

Follow these steps to attach and wire the AC power module.

1. Disconnect power to the terminal.
2. Remove the DC power terminal block currently installed in your terminal.

See

Remove and Install the Power Terminal Block on page 26

.

3. Plug the DC power terminal block connected to the AC power supply

module into the terminal.

4. Insert the two short tabs on the AC module into the slots on the back of

the terminal.

5. Push down on the module until the two long tabs snap into the slots on the

opposite side of the terminal.

Make sure the module is securely connected and that the power supply
wires are not pinched between the module and the terminal.

Follow these steps to connect the AC power to the terminal block module on the
AC module.

1. Secure the AC power wires to the marked terminals (L1 and L2N) on the

power terminal block.

Table 37 - Wire Specifications for Power Terminal Block

Wire Type

Dual-wire Size

(1)

(1) Two-wire max per terminal.

Single-wire Size

Strip Length

Screw Torque

Stranded or solid
Cu 90 °C (194 °F)

0.3…1.3 mm

2

22…16 AWG

0.3…2.1 mm

2

(22…14 AWG)

7 mm (0.28 in.)

0.45…0.56 N•m
(4…5 lb•in)

4

5

Advertising