Rockwell Automation 2711PC-xxxx PanelView Plus 6 Compact Terminals User Manual User Manual
Page 120

120
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
Chapter 5
Install and Replace Components
Follow these steps to attach and wire the AC power module.
1. Disconnect power to the terminal.
2. Remove the DC power terminal block currently installed in your terminal.
Remove and Install the Power Terminal Block on page 26
.
3. Plug the DC power terminal block connected to the AC power supply
module into the terminal.
4. Insert the two short tabs on the AC module into the slots on the back of
the terminal.
5. Push down on the module until the two long tabs snap into the slots on the
opposite side of the terminal.
Make sure the module is securely connected and that the power supply
wires are not pinched between the module and the terminal.
Follow these steps to connect the AC power to the terminal block module on the
AC module.
1. Secure the AC power wires to the marked terminals (L1 and L2N) on the
power terminal block.
Table 37 - Wire Specifications for Power Terminal Block
Wire Type
Dual-wire Size
(1)
(1) Two-wire max per terminal.
Single-wire Size
Strip Length
Screw Torque
Stranded or solid
Cu 90 °C (194 °F)
0.3…1.3 mm
2
22…16 AWG
0.3…2.1 mm
2
(22…14 AWG)
7 mm (0.28 in.)
0.45…0.56 N•m
(4…5 lb•in)
4
5