Install the Terminal

Chapter 2

Earth/Ground Connection

PanelView Plus 6 compact terminals use a DC power input and have an earth/
ground terminal that you must connect to a low-impedance earth/ground:

On 400 and 600 terminals, the earth/ground connection is on the power

terminal block.

On 1000 terminals, the earth/ground connection is on the rear of the

display module.

IMPORTANT

The earth/ground connection to ground is mandatory. This connection is
required for the following:

Noise immunity, reliability, and Electromagnetic Compliance (EMC) with

the European Union (EU) EMC directive for CE-mark conformance

Safety by Underwriters Laboratory

Table 19 - Earth Wire Specifications for DC Power

Terminal

Symbol

Wire Type

Wire Gauge

Terminal Screw Torque

400, 600

GND

Stranded or solid
Cu 90 °C (194 °F)

2.1…3.3 mm

2

(14…12 AWG)

0.45…0.56 N•m
(4…5 lb•in)

1000

GND

Stranded or solid
Cu 90 °C (194 °F)

2.1…5.3 mm

2

(14…10 AWG)

1.13…1.36 N•m
(10…12 lb•in)

ATTENTION: Damage or malfunction can occur when a voltage potential exists
between two separate ground points. Make sure the terminal does not serve as
a conductive path between ground points at different potentials.