Monitors – Rockwell Automation 2711PC-xxxx PanelView Plus 6 Compact Terminals User Manual User Manual
Page 82

82
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
Chapter 4
Windows CE Operating System
Monitors
The Monitors tab of the PanelView Hardware Monitor provides continuous
voltage, temperature, and load information for the terminal.
Battery Voltage
The Monitors tab gives a visual status and voltage reading of the battery for the
real-time clock. The battery voltage is updated at powerup and then every hour.
A low or depleted battery is recorded in the systems events log.
Temperatures
The Monitors tab provides a visual status and current temperature of the logic
board in the terminal. The temperature is updated every 10 seconds.
A failed temperature sensor is recorded in the system events log.
Table 26 - Battery Conditions
Condition
Battery
Depleted
Less than 2.0V indicates a dead battery or no power.
Low
2.0…2.74V
Normal
2.75V or higher
Table 27 - Temperature Conditions
Condition
Logic Board
Low
–
Normal
25…94 °C (77…201 °F)
High
95 °C (203 °F) and higher