82

Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014

Chapter 4

Windows CE Operating System

Monitors

The Monitors tab of the PanelView Hardware Monitor provides continuous
voltage, temperature, and load information for the terminal.

Battery Voltage

The Monitors tab gives a visual status and voltage reading of the battery for the
real-time clock. The battery voltage is updated at powerup and then every hour.

A low or depleted battery is recorded in the systems events log.

Temperatures

The Monitors tab provides a visual status and current temperature of the logic
board in the terminal. The temperature is updated every 10 seconds.

A failed temperature sensor is recorded in the system events log.

Table 26 - Battery Conditions

Condition

Battery

Depleted

Less than 2.0V indicates a dead battery or no power.

Low

2.0…2.74V

Normal

2.75V or higher

Table 27 - Temperature Conditions

Condition

Logic Board

Low

Normal

25…94 °C (77…201 °F)

High

95 °C (203 °F) and higher