Serial Connection

The RS-232 serial port is multi-purpose and supports these connections:

DH-485 communication through a serial connection
DF1 full-duplex communication with controllers using direct connections

or modem connections

Third-party point-to-point communication
Application transfers and printing

The serial port is a 9-pin, male, RS-232 connector.

Table 44

shows the pinout

descriptions and how these pins map to the serial ports on the controllers.

The maximum cable length for serial communication is 15.24 m (50 ft).

6

1

1

6

Insert plastic tie wrap in the hole and
use as strain relief for all attached
cables.

9 8 7 6

5 4 3 2 1

Table 44 - RS-232 Serial Port Connector Pinout

PanelView Plus 6 Compact

RS-232 Port 9-pin DCE

SLC or Logix

9-pin

PLC
25-pin

MicroLogix/
ENI 8-pin DIN

1

2

2

3

4

3

3

2

7

4

4

20

5

5

7

2

6

6

6

7

7

4

8

8

5

9

Connector Shell

Chassis Gnd

WARNING: Do no connect or disconnect communication cable with power
applied to the terminal or the serial device connected to the terminal. An
electrical arc could cause an explosion in hazardous location installations. Be
sure that power is removed or the area is nonhazardous before proceeding.

RXD

TXD

DTR

COM

DSR

RTS

CTS