Installing the LonWorks Module in the Drive

3-11

3.3

Installing the LonWorks Module in
1 to 20 HP@230 VAC Drives

Use this procedure to install the LonWorks module in the drives listed in table 3.4.

Refer to figure 3.6 as you perform this procedure.

!

ATTENTION: Only qualified electrical personnel familiar with the
construction and operation of this equipment and the hazards involved
should install, adjust, operate, or service this equipment. Read and
understand this manual and other applicable manuals in their entirety
before proceeding. Failure to observe this precaution could result in
severe bodily injury or loss of life.

ATTENTION: The drive is at line voltage when connected to incoming
AC power. Disconnect, lock out, and tag all incoming power to the drive
before performing the following procedure. Failure to observe this
precaution could result in severe bodily injury or loss of life.

ATTENTION: DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input power, wait five
minutes for the DC bus capacitors to discharge and then check the
voltage with a voltmeter to ensure the DC bus capacitors are discharged
before touching any internal components. Failure to observe this
precaution could result in severe bodily injury or loss of life.

ATTENTION: The drive contains ESD- (Electrostatic Discharge)
sensitive parts and assemblies. Static control precautions are required
when installing, testing, servicing, or repairing the drive. Erratic machine
operation and damage to, or destruction of, equipment can result if this
procedure is not followed. Failure to observe this precaution can result
in bodily injury.

Table 3.4 – Model Numbers for 1 to 20 HP@230 VAC Drives

VTAC 7 Model Numbers

1H21xx
1H22xx

2H21xx
2H22xx

3H21xx
3H22xx

5H21xx
5H22xx

7H21xx
7H22xx

10H21xx
10H22xx

15H21xx
15H22xx

20H21xx
20H22xx