Rockwell Automation 2LW3000 LonWorks Communication Option Module for VTAC 7 Drives User Manual

Page 63

Advertising
background image

Operating the Drive Using a LonMark Profile

7-11

Minimum Speed

Definition:

network input config SNVT_lev_percent nciMinSpeed

Explanation:

Defines the minimum speed of a motor (around zero). Its value
is entered as a percent of nominal frequency, as defined by the
nominal frequency (nciNmlFreq) configuration value. Set this
parameter when the drive is stopped. NciMinSpeed will be in
effect on the next frequency setting.

If nciNmlFreq = 50 Hz and nciMinSpeed = 10%, the minimum
frequency is 5 Hz.

-163.84

minimum speed

maximum speed

163.83

Default:

Read from drive

Ramp Up Time

Definition:

network input config SNVT_time_sec nciRampUpTm;

Explanation:

Sets the ramp-up time.

Default:

Read from drive

Ramp Down Time

Definition:

network input config SNVT_time_sec nciRmapDownTm;

Explanation:

Sets the ramp-up time. Optionally, this configuration property
can be used to set the ramp-down time.

Default:

Read from drive

Jog Reference

Definition:

network input config SNVT_count nciJog Ref

Explanation:

Set the jog reference for the drive. For reverse operation, set
(nviSpeedScale * nviSpeedStpt.value) negative.

Default:

Read from drive

Scaling:

Scaling: Hz / RPM set in drive: nciJogRef / 10.

Advertising