3 configuration properties (ncis) – Rockwell Automation 2LW3000 LonWorks Communication Option Module for VTAC 7 Drives User Manual

Page 61

Advertising
background image

Operating the Drive Using a LonMark Profile

7-9

7.3

Configuration Properties (NCIs)

This section describes the configuration properties (NCIs).

If an NCI has a corresponding parameter in the drive, it is written to with the value of
the NCI at the following times:

When the NCI is updated from the network

When the node is brought online

When power is cycled to the drive

When the drive is faulted and the error is reset from the LonWorks module.

.

Parameter Value Out

Definition:

network output SNVT_count nvoParam

Explanation:

Used as feedback variable for generic parameter requests. See
nciParRdAddress (section 7.3).

Send Heartbeat

Definition:

network input config SNVT_time_sec nciSndHrtBt

Explanation:

Provides the maximum time between propagates (update of
value to network) for the variable nvoDrvSpeed. This NCI is
overridden by nciMinOutTm. If nciMinOutTm is longer, nothing
will be output, even if nciSndHrtBt has timed out.

Range:

Same as Receive Heartbeat?

Default:

0.0 (Disabled)

Receive Heartbeat

Definition:

network input config SNVT_time_sec nciRcvHrtBt

Explanation:

Selects the maximum time that can elapse between updates of
the input network variable nviDrvSpeedStpt before a fault is
reported to the drive. The drive will handle the fault as specified
by parameter P.062.

The fault can be reset only from the LonWorks module. Set
nviObjRequest to RQ_CLEAR_ALARM

Range:

0.0 (Disabled) to 6,5553.4 seconds

Default:

0.0 (Disabled)