9-2

LonWorks Module for VTAC 7 Drives

9.1.1 Module Status LED

9.1.2 Service LED

9.1.3 Wink LED

Table 9.1 – Module Status LED: State Definitions

LED State

Cause

Corrective Action

Solid green

Normal operation/power on

None required.

Flashing
green

Initialization of AnyBus/VTAC 7
interface

None required.

Flashing red Recoverable fault:

4 Hz:

2 Hz: Heartbeat timeout
received.

1 Hz: Node is offline.

4 Hz: Check that P.061 is set to
1 for full access to all drops.

2 Hz:

1 Hz:

Solid red

Unrecoverable fault (hardware
error).

Replace module.

Table 9.2 – Service LED: State Definitions

LED State

Cause

Corrective Action

Off

This node is configured and
installed in a network.

None required.

Flashing
green

This node has an application, but
it is not yet installed in a network
(unconfigured).

Configure the application.

Solid green

This node is unconfigured and
has no application. Indicates
errors detected by the Neuron
self-test routine.

Configure node and load application.

Table 9.3 – Wink LED: State Definitions

LED State

Cause

Corrective Action

Off

Normal state.

None required.

Flashing red A wink command is received on

the LonWorks network.

None required.

Advertising