Rockwell Automation 2LW3000 LonWorks Communication Option Module for VTAC 7 Drives User Manual

Page 38

Advertising
background image

3-24

LonWorks Module for VTAC 7 Drives

Step 4.2 Align the LonWorks module on the four mounting tabs on the keypad

bracket. Make sure that the ribbon cable is not pinched between the keypad
bracket and the LonWorks module.

Step 4.3 Fasten the LonWorks module to the right side of the keypad bracket using

the two metal M3 screws and lock washers for proper grounding. Fasten the
left side using the two 6-32 screws and lock washers for proper grounding.

Important: You must use the lock washers to properly ground the LonWorks module.

Improper grounding of the LonWorks module can result in erratic operation
of the drive.

Step 4.4 Realign the 26-conductor ribbon cable connector with the Power Supply

board connector inside the slot in the keypad support bracket. Carefully
press the ribbon cable connector in until the retaining clips lock it into place.

Step 5.

Reinstall the Keypad Bracket in the Drive

Step 5.1 Reconnect the keypad bracket to the keypad support bracket by inserting

the mounting tabs into the slots in the keypad support bracket and tightening
the thumb screw.

Step 5.2 Reconnect any wiring that was removed from the Regulator board terminal

strip. Refer to the terminal connections documented in step 3.1 or to the
appropriate instruction manuals for the devices being used.

Step 5.3 NEMA 4X/12 drives only: Before installing the cover, check that the gaskets

on the cover are flat and within the gasket channels.

Step 5.4 Reinstall the cover. Align all cover screws into the heat sink before

tightening any of them.

Figure 3.13 – LonWorks Module Location in 25 to 60 HP @ 460 VAC Drives

Regulator Board

LonWorks
Module

Front View

Top View