152 Socket Interface

where:

MSG Source Length

Specify 16 bytes (Timeout + Addr + BufLen) + number of bytes to
write

MSG Destination Element

The MSG instruction returns the number of bytes that were written.
Specify a DINT tag.

Considerations

See Programming Considerations on page 135 for more information.

Element

Data Type

Description

Timeout

DINT

Specify the timeout in milliseconds

ToAddr

structure

A user-defined structure that specifies the address to write.

Family

INT

Specify the address family. Must be 2.

Port

INT

Specify a local port number, or set to 0 (the local port number will be
chosen by the web server). For TCP client operations, specify 0 unless
you want a specific local port number. For TCP server communications,
specify the port number on which to accept incoming connection
requests. For UDP, to receive datagrams on a specific port, you must
specify a local port number.

Addr

DINT

Specify an IP address. Typically, set to 0 (any address).

BufLen

DINT

Specify the number of bytes of data to write.

Buf

SINT array

Specify the data to write.

Advertising