Troubleshoot socket applications, Debugging hints and tips – Rockwell Automation 1768-EWEB EtherNet/IP Web Server Module User Manual User Manual

Page 160

Advertising
background image

Publication ENET-UM527E-EN-P - October 2006

160 Socket Interface

Troubleshoot Socket
Applications

To help debug and troubleshoot applications, the socket interface
provides a set of web pages, located in the web server’s Advanced
Diagnostics folder.

Debugging Hints and Tips

Web Page

Description

Socket Object Diagnostics

Displays information about on each existing instance:

• Instance number
• Socket type – client, server, or listen
• Local and remote ports and IP addresses
• Send and receive buffer sizes
• Socket up time and inactivity time
• Socket state and last error state

Socket Object Statistics

Displays attribute settings for each instance

Socket Object Log

Displays a log of service requests (maximum of 50 log entries):

• Service requests made to the socket object
• For each request, shows parameters passed and the result of service (success / failure)

You can enable/disable logging for some services by setting Class attribute #8 (Log
Enable). See Socket Object Class Attributes on page 158.

Category

Consideration

Web server module

Make sure the web server module has a valid IP address. Also, if you communicate with
devices on different subnets, configure the web server with a valid subnet mask and
gateway address.

CreateSocket service

Make sure the Destination tag is of type of DINT.

After creating the socket with the CreateSocket service, make sure you use the instance
number that CreateSocket returns in the subsequent socket services you call.

MSG instruction

Make sure the Source Element is of a type that matches the request parameters for the
requested service. Also make sure the Source Length is the correct length for the service
parameters.

There is a limit to the number of active MSG instructions in a Logix controller. If a MSG
instruction is enabled and exceeds the maximum number of active MSG instructions, the
MSG instruction receives an error (.ER bit set).

OpenConnection service

Make sure the Source Length includes the size of the Timeout parameter + Address Length
parameter + the Length of the address itself.