74 Send Email

where:

On the Communication tab of the MSG instruction, configure the path
from the controller to the web server module.

The path starts with the controller initiating the MSG instruction
module. Then enter the port the message exits and the address of the
next module in the path. For example, if the web server module is in
the same chassis as the controller and is in slot 2, the path is: 1, 2.

If all the devices in the path are configured in the initiating controller’s
I/O Configuration tree, you can use the Browse button to select the

In This Field

Enter

Service Type

Custom

Service Code

4b

Instance

1

Class

32f

Attribute

0

Source Element

The tag that contains the email text

This tag is of the STRING data type you created to contain the email text. In this example,
enter EWEB_EMAIL which is of type EmailString

Source Length

The number of characters in the email text plus 4

In this example, enter 69 (65 characters in the email + 4)

Destination

A tag to contain the status of the email transmission

This tag is also of the STRING data type you created to contain the email text. In this
example, enter EmailDstStr which is of type EmailString