Publication ENET-UM527E-EN-P - October 2006

78 Manage User Accounts and Access Levels

Configure Access Limits
For Web Pages

You protect individual web pages and data views on a per URL basis.
Each page in the web server module has one of these protection
levels:

• Administrator
• Write
• Read

The protection levels are hierarchical. Administrator users can access
Write and Read protected pages, and Write users can access Read
protected pages.

These predefined pages (those web pages that come with the web
server module) in the web server module have these default access
levels. You can change these access levels, if needed.

In Data Views, the access limits you specify for a tag applies to the
whole data view, not just the tag. If you have multiple tags with
different access levels in the same data view, the web server assigns
the highest (most access) level to the data view. For more information,
see chapter 3.

If you develop custom web pages, you must explicitly specify the
access limits for the page if you want access protection. Otherwise,
the custom web page will have no access limits.

You need Administrator access to modify access limits for web pages.
You specify the access limit for a web page by selecting
Administrative Settings

> User Management > Edit Access Limits.

Web Page

Required Protection Level

Home page

No protection

Diagnostics pages

Chassis Browse page

Data Views with read-only tags

Read protection

Data Views with write tags

Write protection

Data Views with administrator tags

Administrator protection

Device configuration pages

Server Management page

User Management page

Send Email page