MC2: 04/23/13 Page 120 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

Table G-4: ACS Commands

No.

COMMAND

ENTRY RANGE

FACTORY

DEFAULT

00

Header Temperature (°F)

40 to 220

Read Only

01

Outside Air Temperature (°F)

-60 to 80

Read Only

02

Return Sensor (°F)

40 to 160

Read Only

03

Percent of Load (%)

0 to 100

Read Only

04

Header Set Temperature (°F)

40 to 220

Read Only

05

System Start Temperature (°F)

32 to 120

70

06

System Start Mode

0 = Temp Only

1 = Temp and Load

0 = Temp Only

07

Internal Setpt (°F)

40 to 220

160

08

Bldg Reference Temperature (°F)

40 to 220

70°F

09

Not Used

10

Not Used

11

Reset Ratio

0.3 to 3.0

(0.1 increments)

1.2

12

Maximum Header Temperature (°F)

40 to 220

220

13

Minimum Header Temperature (°F)

40 to 220

40

14

Boiler Start Percent

25 to 100

20

15

Boiler Stop Percent

10 to 45

16

16

Integral Gain (Rep./Min)

0.00 to 9.99

(0.01 increments)

0.15

17

Header Set Mode

0 = Constant Setpt

1 = Indr/Outdr Reset

2 = Remote Settemp

0 = Constant Setpt

18

Derivative Gain

-2.00 to 2.00

(0.01 increments)

0.15

19

Proportional Band (°F)

5 to 100

70

20

Aux Relay Open

0 to 99

45

21

Aux Relay Close

0 = 100% Fire Rate

1 = 100% and OFF

1 = 100% AND OFF

22

Failsafe Mode

0 = Shutdown

1 = Switch Inputs

0 = Shutdown

23

Fault Relay Mode

0 = All Faults

1 = No Interlock

2 = Interlock 2

3 = Interlock 1

0 = All Faults

24

Alarm Clear Method

0 = Automatic

1 = Manual

0 = Automatic

25

Boiler Operation Mode

0 = Parallel

1 = Sequential

2 = Combination

1 = Sequential