5 entering system start temperature, 6 entering boiler start and boiler stop levels, Entering system start temperature – AERCO Control System (ACS) User Manual

Page 70: Entering boiler start and boiler stop levels, Gf-131 aerco control system (acs)

Advertising
background image

MC2: 04/23/13 Page 70 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

4.2.5 Entering System Start Temperature

In order to set up the Outdoor Reset Mode, the System Start Temperature must be entered. The

System Start Temperature is the outside air temperature at which the boiler plant begins to

operate. The factory default value for the System Start Temperature (SYS START TEMP) is

70°F. However, temperatures from 32°F to 120°F can be selected using the ▲ and ▼ arrow

keys on the ACS keypad. Proceed as shown below:

4.2.6 Entering Boiler Start and Boiler Stop Levels

The Boiler (BLR) Start and Boiler Stop Levels are also entered in the Configuration Menu. Refer

to Appendix I to determine the correct Start and Stop levels for your installation. Enter the

appropriate values in the Configuration Menu as shown below:



Entering Boiler Start & Boiler Stop Levels

1. Press the

MENU key until RELAY MENU appears in the display.

2. Press the ▲ arrow key once. SYS START TEMP will be displayed along with the current

setting for the System Start Temperature.

3. Press the

CHANGE key to change the displayed temperature. The display will switch to a

reverse video format.

4. Select the desired System Start temperature using the ▲ or ▼ arrow key.
5. Press the

ENTER key to store the changed temperature. The reverse video display will

revert to the normal VFD display format.

Entering System Start Temperature

1. Using the ▲ or ▼ arrow key on the keypad, scroll through the Configuration Menu until

BLR START LEVEL is displayed along with the current setting (default = 20%).

2. If the desired Boiler Start Level is not displayed, press the

CHANGE key. The display will

switch to to a reverse video format.

3. Select the desired Boiler Start Level using the ▲ or ▼ arrow key.
4. Press the

ENTER key to store the changed Start Level.. The reverse video display will

revert to the normal VFD display format.

5. Next, scroll through the menu until the BLR STOP LEVEL is displayed along with the

current setting (default = 16%).

6. If the desired Boiler Stop Level is not displayed, repeat steps 2, 3 and 4 above and enter

the desired Stop Level.