MC2: 04/23/13 Page 87 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

Table A-1: ACS Menus - Continued

MENU LEVEL & OPTION

AVAILABLE CHOICES OR

LIMITS

DEFAULT

MINIMUM

MAXIMUM

FIELD ADJUST MENU

HEADER SET MODE

CONSTANT SETPOINT,

OUTDOOR RESET,

REMOTE SETPOINT

CONSTANT

SETPOINT

HDR HIGH LIMIT

040°F

220°F

200°F

HDR LOW LIMIT

040°F

220°F

040°F

INTERNAL SETPT

040°F

220°F

160°F

RESET RATIO

(Displayed Only if

HDR SET MODE = OUTDOOR RESET)

0.3

3.0

1.2

BLDG REF TEMP (Displayed Only If

HDR SET MODE = OUTDOOR RESET)

40°F

220°F

70°F

REMOTE SIGNAL (Displayed Only If

HDR SET MODE = REMOTE SETPT)

4 – 20 mA,

MODBUS

4 - 20 mA

OFFSET ENABLE

OFF, ON

OFF

SUN

OFFS TEMP

-50.0°F

50.0°F

00.0

SUN ON HOUR

00

23

00

SUN ON MINUTE

00

59

00

SUN OFF HOUR

00

23

00

SUN OFF MINUTE

00

59

00

Etc., Up To:

SAT OFF MINUTE

00

59

00

OFFSET ENABLE

OFF, ON

OFF

SUN OFFS TEMP

-50.0°F

50.0°F

00.0

SUN ON HOUR

00

23

00

SUN ON MINUTE

00

59

00

SUN OFF HOUR

00

23

00

SUN OFF MINUTE

00

59

00

Etc., Up To:

SAT OFF MINUTE

00

59

00