8 sample rs485 (modbus) network diagrams, Gf-131 aerco control system (acs) – AERCO Control System (ACS) User Manual

Page 30

Advertising
background image

MC2: 04/23/13 Page 30 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

2.8 SAMPLE RS485 (MODBUS) NETWORK DIAGRAMS

Figure 2-10 shows a sample RS485 (Modbus) Network diagram with the ACS connected to

KC1000 or Benchmark Series Boilers equipped with C-More Control Systems.

Figure 2-11

shows a similar sample diagram with the ACS connected to Modulex Series Boilers equipped

with BCMs and E8 Controllers.

Figure 2-10: Sample RS485 (Modbus) Network For Benchmark or KC1000 Boilers


Figure 2-11: Sample RS485 (Modbus) Network For Modulex Series Boilers

NOTE

The last C-More slave on the RS485 loop

must have its termination resister (TERM)

and bias (BIAS1, BIAS2) DIP Switches

turned on. Refer to Section 2.7 of this

manual for details on activating bias and

termination.

NOTE

The last BCM slave on the RS485 loop

must have its termination resister (T)

activated. Refer to GF-115C for more

information.
The bias switches in the ACS should both

be turned to “ON”.