MC2: 04/23/13 Page 89 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

Table A-1: ACS Menus - Continued

AVAILABLE CHOICES OR LIMITS

MENU LEVEL & OPTION

MINIMUM

MAXIMUM

DEFAULT

TUNING MENU

PROPORTIONAL BND

005°F

120°F

070°F

INTEGRAL GAIN

0.00 REP/MIN

9.99 REP/MIN

0.15 REP/MIN

DERIVATIVE GAIN

-2.00 MIN.

2.00 MIN.

0.15 MIN.

HIGH DB SETPT ENABLE

BLR STOP PCT

100%

16%

DEADBND HIGH

001°F

025°F

001°F

DEADBND LOW

001°F

015°F

001°F

SETPOINT DOWN RATE

1° PER MIN

240° PER MIN

100° PER MIN

DEMAND OFFSET

0°F

25°F

0°F

RELAY MENU

SYS START TEMP

032°F

120°F

070°F

SYS START OPTION

TEMP ONLY,

TEMP AND LOAD

TEMP ONLY

SYS START INTLK

DISABLED

INTERLOCK 1

INTERLOCK 2

INTERELOCK 1&2

INTERLOCK 1

AUX RELAY OPEN

000%

099%

045%

AUX RELAY CLOSE

100% FIRE RATE,

100% AND OFF

100% AND OFF

FAULT ALRM RELAY

ALL FAULTS,

NO INTERLOCK,

INTERLOCK 2,

INTERLOCK 1

ALL FAULTS

FAULT ALARM BLRS

NO BLR FAULTS,

ALL BLR FAULTS

NO BLR FAULTS

FAULT ALRM CLEAR

AUTOMATIC,

MANUAL RESET

AUTOMATIC