MC2: 04/23/13 Page 122 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

Table G-4: ACS Commands - Continued

No.

COMMAND

ENTRY RANGE

FACTORY

DEFAULT

26

Not Used

27

28

29

Reserved

30

Maximum Power Input

50 to 100

100

31

System Interlock Configuration

0 = Always Enabled

1 = Start Enabled

1 = Start Enabled

32

Real Time Clock - Minutes

00 to 59

Present Time

33

Real Time Clock - Hours

00 to 23

Present Time

34

Real Time Clock - Day Of Week

1 to 7

Present Day

35

Real Time Clock - Year

00 to 99

Present Year

36

Real Time Clock - Day Of Month

00 to 31

Present Day

37

Real Time Clock - Month

00 to 12

Present Month

38

(Day 1 – Sun.)

Thru

Offset Temperatures (Day 1-7)

-50 to +50°F

All Set To 0°F

44

(Day 7 – Sat.)

45

(Sun.)

Thru

Offset ON Time – Minutes (Sun.-Sat.)

00 to 59

All Set to Zero

51

(Sat.)

52

(Sun.)

Thru

Offset ON Time – Hours (Sun.-Sat.)

00 to 23

All Set To Zero

58

(Sat.)

59

Offset Enable

0 = Disabled

1 = Enabled

0 = Disabled

60

Header Temp Offset (°F)

-10°F to 10°F

0

61

System Start Interlock

1 = Intlk 1 Opens

Start Relay

2 = Intlk 2 Opens Start

Relay

3 = Either Intlk Opens

Start Relay

1 = Intlk 1

70

(Sun.)

Thru

Offset OFF Time – Minutes (Sun.-Sat.)

00 to 59

All Set To Zero

76

Sat.)

77

(Day 1)

Thru

Offset OFF Time – Hours (Day 1-7)

0 to 23

All Set To Zero

83

(Day 7)

84

(Reserved)

85

Not Used

0 or 1