Gf-131 aerco control system (acs) – AERCO Control System (ACS) User Manual
Page 125

MC2: 04/23/13 Page 125 of 144
GF-131
AERCO Control System (ACS)
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
Installation, Operation, and Maintenance Manual
OMM-0081_0D
Table G-4: ACS Commands - Continued
No.
COMMAND
ENTRY RANGE
FACTORY DEFAULT
129
Modbus Pass-Thru
0 = Disabled
1 = Enabled
0 = Disabled
130
Header Temp Deadband
01 to 15°F
05°F
131
Outside Temp Sensor Offset
-10.0°F to 10.0°F
0.0°F
132
Ramp Up %/Min
000 to 300
20
133
Ramp Down %/Min
000 to 300
200
134
Fault Alarm Boilers
No Blr Faults
All Blr faults
No Blr Faults
135
4-20 mA Offset
-1.00 to 1.00 mA
0.0 mA
136
Return Sensor Offset
-10.0 to 10.0°F
0.0°F
137
Load Start Pct
000 to 100
1
138
Load Stop Pct
000 to 100
0
150
I/O Status
00 to 255
Bit 0 = AUX Relay
Bit 1 = Fault Relay
Bit 2 = Sys Start Relay
Bit 3 = Empty
Bit 4 = Setback
Bit 5 = Interlock 2
Bit 6 = Interlock 1
Bit 7 = Empty
151
&
Up
(Reserved For Future Expansion)
Undefined