3.14.2 REMOTE SETPT MODE:

Perform the procedure described for the CONSTANT SETPT MODE and then continue with the

steps described below:

MENU & OPTION

ACTION

1. FIELD ADJUST MENU

HEADER SET MODE

Set to REMOTE SETPT

HDR HIGH LIMIT

Enter the maximum temperature for the Remote Setpoint input

(this will be the temperature equivalent to a 20 mA input) Default

= 200°F

HDR LOW LIMIT

Enter the minimum temperature for the Remote Setpoint input

(this will be the temperature equivalent to a 4 mA input) Default =

40°F

REMOTE SIGNAL

Select 4-20 mA (default) or MODBUS

2. CONFIGURATION MENU

FAIL SAFE MODE

Set to CONSTANT SETPT if you want to maintain a Constant

Setpoint temperature in the event that the Remote signal is lost.

(Default = SHUTDOWN)