2 remote setpt mode, Remote setpt mode, Gf-131 aerco control system (acs) – AERCO Control System (ACS) User Manual
Page 65

MC2: 04/23/13 Page 65 of 144
GF-131
AERCO Control System (ACS)
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
Installation, Operation, and Maintenance Manual
OMM-0081_0D
3.14.2 REMOTE SETPT MODE:
Perform the procedure described for the CONSTANT SETPT MODE and then continue with the
steps described below:
MENU & OPTION
ACTION
1. FIELD ADJUST MENU
HEADER SET MODE
Set to REMOTE SETPT
HDR HIGH LIMIT
Enter the maximum temperature for the Remote Setpoint input
(this will be the temperature equivalent to a 20 mA input) Default
= 200°F
HDR LOW LIMIT
Enter the minimum temperature for the Remote Setpoint input
(this will be the temperature equivalent to a 4 mA input) Default =
40°F
REMOTE SIGNAL
Select 4-20 mA (default) or MODBUS
2. CONFIGURATION MENU
FAIL SAFE MODE
Set to CONSTANT SETPT if you want to maintain a Constant
Setpoint temperature in the event that the Remote signal is lost.
(Default = SHUTDOWN)