Gf-131 aerco control system (acs) – AERCO Control System (ACS) User Manual

Page 136

Advertising
background image

MC2: 04/23/13 Page 136 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

Table H-2: ACS Standard Holding Register Address Mapping - Continued

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

32 (0x0020) Real Time Clock

Minutes

00 to 59

Present Time

33 (0x0021) Real Time Clock

Hours

00 to 23 Hours

Present Time

34 (0x0022) Real Time Clock

Day of Week

1 to 7

Present Day

35 (0x0023) Real Time Clock

Year

00 to 99

Present Year

36 (0x0024) Real Time Clock

Day of Month

01 to 31

Present Day of Month

37 (0x0025) Real Time Clock

Month

01 to 12

Present Month

38 (0x0026) Offset Temp Sun.

-50 to 50°F

Default = 0°F

39 (0x0027) Offset Temp Mon.

-50 to 50°F

Default = 0°F

40 (0x0028) Offset Temp Tue.

-50 to 50°F

Default = 0°F

41 (0x0029) Offset Temp Wed.

-50 to 50°F

Default = 0°F

42 (0x002A) Offset Temp Thu.

-50 to 50°F

Default = 0°F

43 (0x002B) Offset Temp Fri.

-50 to 50°F

Default = 0°F

44 (0x002C) Offset Temp Sat.

-50 to 50°F

Default = 0°F

45 (0x002D) Offset On Time

Day 1 – Minutes

00 to 59 Minutes

Default = o

46 (0x002E) Offset On Time

Day 2 – Minutes

00 to 59 Minutes

Default = 0

47 (0x002F) Offset On Time

Day 3 – Minutes

00 to 59 Minutes

Default = 0

48 (0x0030) Offset On Time

Day 4 – Minutes

00 to 59 Minutes

Default = 0

49 (0x0031) Offset On Time

Day 5 – Minutes

00 to 59 Minutes

Default = 0

50 (0x0032) Offset On Time

Day 6 – Minutes

00 to 59 Minutes

Default = 0

51 (0x0033) Offset On Time

Day 7 – Minutes

00 to 59 Minutes

Default = 0

Advertising