5 entering boiler start & stop levels, 4 constant setpoint mode, Entering boiler start & stop levels – AERCO Control System (ACS) User Manual

Page 74: Gf-131 aerco control system (acs)

Advertising
background image

MC2: 04/23/13 Page 74 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

4.3.5 Entering Boiler Start & Stop Levels

The Boiler (BLR) Start and Boiler Stop Levels are also entered in the Configuration Menu. Refer

to Appendix I to determine the correct Start and Stop levels for your installation. Enter the

appropriate values in the Configuration Menu as shown below:

4.4 CONSTANT SETPOINT MODE

In the Constant Setpoint Mode of operation, only a header sensor is required. Entries in this

mode are required for the following items:

FIELD ADJUST MENU

HEADER SET MODE
INTERNAL SETPOINT

CONFIGURATION MENU

BOILER OPERATING MODE
BLR START LEVEL
BLR STOP LEVEL

The set-up instructions for the above menu options are provided in paragraphs which follow.










Entering Boiler Start & Stop Levels

1. Using the ▲ or ▼ arrow key on the keypad, scroll through the Configuration Menu until

BLR START LEVEL is displayed along with the current setting (default = 20%).

2. If the desired Boiler Start Level is not displayed, press the

CHANGE key. The display will

switch to a reverse video format.

3. Select the desired Boiler Start Level using the ▲ or ▼ arrow key.
4. Press the

ENTER key to store the changed Start Level.. The reverse video display will

revert to the normal VFD display format.

5. Next, scroll through the menu until the BLR STOP LEVEL is displayed along with the

current setting (default = 16%).

6. If the desired Boiler Stop Level is not displayed, repeat steps 2, 3 and 4 above for the

desired Stop Level.