Table A-1: ACS Menus - Continued
AVAILABLE CHOICES OR LIMITS
MENU LEVEL & OPTION
MINIMUM
MAXIMUM
DEFAULT
CALIBRATION MENU
HDR SENS OFFSET
-10.0°
10.0°
00.0°
OUTD SENS OFFSET
-10.0°
10.0°
00.0°
4 – 20 MA OFFSET
-10.0
10.0
00.0
RET SENS OFFSET
-10.0°
10.0°
00.0
RAMP UP %/MIN
000
300
020
RAMP DOWN %/MIN
000
300
200
RESET DEFAULTS
NO,
YES (DONE If Selected)
NO
PASSTHRU WRITE?
DISABLED, ENABLED
DISABLED
VALVE WAIT TIME
1 TO 500 SEC
120 SEC