MC2: 04/23/13 Page 140 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

Table H-2: ACS Standard Holding Register Address Mapping - Continued

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

112 (0x0070) Net Boiler 21

Address

Address for Network Boiler 21

Default = 0

113 (0x0071) Net Boiler 22

Address

Address for Network Boiler 22

Default = 0

114 (0x0072) Net Boiler 23

Address

Address for Network Boiler 23

Default = 0

115 (0x0073) Net Boiler 24

Address

Address for Network Boiler 24

Default = 0

116 (0x0074) Net Boiler 25

Address

Address for Network Boiler 25

Default = 0

117 (0x0075) Net Boiler 26

Address

Address for Network Boiler 26

Default = 0

118 (0x0076) Net Boiler 27

Address

Address for Network Boiler 27

Default = 0

119 (0x0077) Net Boiler 28

Address

Address for Network Boiler 28

Default = 0

120 (0x0078) Net Boiler 29

Address

Address for Network Boiler 29

Default = 0

121 (0x0079) Net Boiler 30

Address

Address for Network Boiler 30

Default = 0

122 (0x007A) Net Boiler 31

Address

Address for Network Boiler 31

Default = 0

**123 (0x007B) Net Boiler 32

Address

Address for Network Boiler 32

Default = 0

124 (0x007C) Network Baud

0=2400, 1=4800, 2=9600, 3=14400,

4=19200

2 = 9600

125 (0x007D) Network Timeout

5 to 240 sec

Default = 60

sec.

126 (0x007E) Password Lo

0 to 255 (73)

Default = 0

127 (0x007F) Password Hi

0 to 255 (79)

Default = 0

128 (0x0080) Modbus Control

Type

0 = Round-Robin

1 = Broadcast

Default = 0

(Round Robin)

129 (0x0081) Modbus Pass-Thru

0 = Disabled

1 = Enabled

Default = 0

(Disabled)

130 (0x0082) RESERVED

Only for BMS II