1 constant setpt mode (default), Constant setpt mode (default), Gf-131 aerco control system (acs) – AERCO Control System (ACS) User Manual

Page 64

Advertising
background image

MC2: 04/23/13 Page 64 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

3.14.1 CONSTANT SETPT MODE (Default):

MENU & OPTION

ACTION

1. SETUP MENU

ENTER PASSWORD

Enter 159

2. RS485 MENU

Enter this menu if there are more than 2 boilers (default), otherwise go to

step 3

NUMBER NETW

BOILERS

This setting is preset to 2. If more than 2 Boilers (default), enter number

(03, 04, etc)

NETW BOILER 01

ADDRESS= 001

Address 001 and 002 are preset. Enter other Network Addresses if

required (003, 004, 005, etc.)

3. FIELD ADJUST MENU If Setpt is other than 160°F (default), enter this menu; otherwise go to

step 4

INTERNAL SETPT

Enter Setpoint temperature

4. CONFIGURATION

MENU

If BLR START LEVEL=20% & BLR STOP LEVEL=16%, skip this menu.

BLR START LEVEL

Enter Boiler Start Level Percent (default = 20%). See Appendix I.

BLR STOP LEVEL

Enter Boiler Stop Level Percent (default = 16%). See Appendix I.