Installation, Operation, and Maintenance Manual

OMM-0081_0D

Table 5-1: Fault Messages (Cont.)

Fault Message

Description & Possible cause

CURRENT LOOP

ERROR

The 4-to-20-mA remote input signal has dropped below 3 mA, or the

signal is not present at the ACS.

FAIL SAFE MODE

ACTIVATED

This message indicates that the ACS is operating in the Fail Safe

(Constant Setpoint) mode.due to sensor loss or signal loss.

MODBUS TIMEOUT

ERROR

Displayed during Modbus Remote Setpoint operation when the ACS is

functioning as a Slave to an EMS Master. Error indicates that the

Network Timeout has expired.

NETWORK DISABLED

MODBUS LISTEN

Displayed during Modbus operation when the “FORCE LISTEN

ONLY” Modbus diagnostic command is sent to the ACS Slave by the

controlling Master, thereby disabling normal Modbus Network

communication. It indicates that the ACS is listening for the

“RESTART COMMUNICATIONS OPTIONS” diagnostic command

required to restart normal Modbus communication. The ACS will

operate in the Fail Safe mode during this period.

VALVE POSITION

ISSUE ERROR

For Option 1 or Option 2, the motorized valve has not reached its

expected position on time. Valve wait time has been exceeded.

FAULT ALARM

BOILER ERROR

A boiler connected to the ACS is in fault.