MC2: 04/23/13 Page 31 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

2.9 RS485 WIRING AT THE ACS

The ACS communicates with an external Energy Management System (EMS) or Building

Automation System (BAS) utilizing the wiring terminals labeled RXD (Receive Data), TXD

(Transmit Data) and 232 ISO GND (Isolated Ground). If the EMS does not contain an RS232

port, a RS485-to-RS232 Converter (AERCO Part No. 124943) is required to communicate with

the ACS. If a Converter is required, it can be installed inside the wiring compartment of the ACS,

or installed externally. The ACS provides an isolated 12 VDC output terminal (ISO 12V) which

can be used to power AERCO’s RS485-to-RS232 Converter if needed. Refer to

Figure 2-12 for

sample network layouts.

Figure 2-12: Sample Network Connections To EMS