1 selecting constant setpoint mode, 2 selecting internal setpoint temperature, Selecting constant setpoint mode – AERCO Control System (ACS) User Manual

Page 75: Selecting internal setpoint temperature, Gf-131 aerco control system (acs)

Advertising
background image

MC2: 04/23/13 Page 75 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

4.4.1 Selecting Constant Setpoint Mode

The Constant Setpoint Mode is selected using the Header Set Mode option in the Field Adjust

Menu as shown below:

4.4.2 Selecting Internal Setpoint Temperature

The Internal Setpoint Temperature is selected using in the Field Adjust Menu below:

Selecting Constant Setpoint Mode

1. Using the keypad on the ACS, press the

MENU key, until FIELD ADJUST MENU

appears in the display.

2. Using the ▲ or ▼ arrow key on the keypad, scroll through the menu until HEADER SET

MODE is displayed in the first line of the VFD display. The second line of the display will

show the currently selected Header Set Mode (CONSTANT SETPOINT, OUTDOOR

RESET or REMOTE SETPOINT).

3. If CONSTANT SETPOINT is not displayed in the second line of the display, press the

CHANGE key. The VFD display will switch to a reverse video format indicating that a

change is in process.

4. Using the ▲ or ▼ arrow key, select CONSTANT SETPOINT.
5. Press the ENTER key to store the change. The reverse video display will revert to the

normal display format indicating that the change has been store in memory. With the

ACS still in the FIELD ADJUST MENU, proceed to next paragraph to select the Internal

Setpoint Temperature.

Selecting Internal Setpoint Temperature

1. Using the ▲ or ▼ arrow key on the keypad, scroll through the menu until INTERNAL

SETPT is displayed in the first line of the VFD display. The second line of the display

will show the currently selected Internal Setpoint temperature (default = 160°F). If the

required INTERNAL SETPT is not displayed in the second line of the display, press the

CHANGE key. The VFD display will switch to a reverse video format indicating that a

change is in process.

2. Using the ▲ or ▼ arrow key, select required INTERNAL SETPT temperature.
3. Press the

ENTER key to store the change. The reverse video display will revert to the

normal display format indicating that the change has been store in memory.

4. This completes the required entries in the Field Adjust Menu. To complete the Constant

Setpoint Mode set-up, select the Boiler Operating Mode as described below.