Installation, Operation, and Maintenance Manual

OMM-0081_0D

4.3.2 Entering Header High Limit and Low Limit Temperatures

The Header High Limit and Header Low Limit are also selected using options in the Field Adjust

Menu as shown below:

NOTE

If the Remote Signal is set to 4 – 20 mA, the HDR HIGH LIMIT

temperature defines the 20 mA value and the HDR LOW LIMIT

temperature defines the 4 mA value.












Entering Header High Limit and Low Limit Temperatures

1. Using the ▲ or ▼ arrow key on the keypad, scroll through the menu until HDR HIGH

LIMIT is displayed in the first line of the VFD display. The second line of the display will

show the currently selected Header High Limit temperature (default = 200°F).

2. If the required HDR HIGH LIMIT is not displayed in the second line of the display, press

the

CHANGE key. The VFD display will switch to a reverse video format indicating that a

change is in process.

3. Using the ▲ or ▼ arrow key, select required HDR HIGH LIMIT temperature.
4. Press the

ENTER key to store the change. The reverse video display will revert to the

normal display format indicating that the change has been store in memory.

5. Next, scroll through the FIELD ADJUST MENU until HDR LOW LIMIT is displayed in the

first line of the VFD display. The second line of the display will show the currently

selected Header Low Limit temperature (default = 040°F).

6. If the required HDR LOW LIMIT is not displayed, press the

CHANGE key.

7. Using the ▲ or ▼ arrow key, select required HDR LOW LIMIT temperature. Press the

ENTER key to store the change.

8. With the ACS still in the FIELD ADJUST MENU, proceed to the next paragraph and

continue the set-up procedure.