2.16 RELAY PANEL COMPONENTS

2.16.1 Power

The power connector is located at the left side of the wiring panel. It uses single phase AC

power from 110 to 240 VAC, 60 Hertz.

2.16.2 Inputs

The inputs are all dry switch (digital) inputs. The specifics are below:

Aquastat In (Temperature) Switch

This switch input comes from the aquastat temperature switch located in the DWH

storage tank. The switch should have at least a 3 degree hysteresis or deadband.

Valve End Switch In 1 & 2

These switch inputs come from the end switches of Valve 1 and Valve 2, respectively.

The valve end switches should close when the valves are completely open.

Aux Relay Contact In

This switch input comes from the dry contact “Aux Relay” output of the ACS.

Sys Relay Contact In

This switch input comes from the dry contact “Sys Relay” output of the ACS.

2.16.3 Outputs

The relay outputs are all dry contact and can switch up to 5A at 120VAC, or ?240 VAC. The

switch outputs connect directly to the ACS and are all dry contacts. The specifics are below:

DHW Pump Relay

This SPST relay is used to activate a DHW pump when the DHW Aquastat is calling for

heat. When the Aquastat stops calling, the relay will remain activated for ?1 minute

before turning off.

Valve I Relay

This SPDT relay controls the valve between the Building Priority boilers and the DHW

Priority boilers. The Normally Open (N.O.) contact is connected to the Valve 1 Open

and the Normally Closed (N.C.) contact is connected to the Valve 1 Close input. For a

valve with “spring return open” or “capacitor return open”, the N.O. contact would not be

used.

Valve 2 Relay

This SPDT relay controls the valve between the Building boilers and the Building Priority

boilers. The Normally Open (N.O.) contact is connected to the Valve 2 Close and the

Normally Closed (N.C.) contact is connected to the Valve 2 Open input. For a valve with

“spring return open” or “capacitor return open”, the N.C. contact would not be used.
Interlock 1
4 Relay – These are 4 SPST relays used to enable or disable the Building Priority boilers

in this 2-valve system.

Aquastat Switch Out

This SPST contact connects to the “Setback” input of the ACS.

Valve End Switch Out

This SPST contact connects to the “Interlock 1” input of the ACS.