Gf-131 aerco control system (acs) – AERCO Control System (ACS) User Manual

Page 86

Advertising
background image

MC2: 04/23/13 Page 86 of 144

GF-131

AERCO Control System (ACS)

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

Installation, Operation, and Maintenance Manual

OMM-0081_0D

Table A-1: ACS Menus - Continued

MENU LEVEL & OPTION

AVAILABLE CHOICES OR LIMITS

DEFAULT

MINIMUM

MAXIMUM

RS232 MENU

RS232 MODE

MODBUS SLAVE, NORMAL

MODBUS SLAVE

RS232 BAUDRATE

2400, 4800, 9600, 19200

9600

MODBUS ADDRESS

128

247

128

NETWORK TIMEOUT (Seconds)

005

240

060

MODBUS PASS THRU

DISABLED, ENABLED

DISABLED

RS485 MENU

RS485 BAUDRATE

2400, 4800,

9600, 19200

9600

MIN SLAVE ADDR

000

127

000

MIN SLAVE ADDR

000

127

000

NUMBER NETW BLRS

00

32

02

MODBUS CNTL TYPE

ROUND ROBIN, BROADCAST

ROUND ROBIN

NETW BOILER 01

ADDRESS =

000

127

001

NETW BOILER 02

ADDRESS =

000

127

002

NETW BOILER 03

ADDRESS =

000

127

000

Etc., Up To:

NETW BOILER 32

ADDRESS =

000

127

000