H.2 ACS CONTROLLER STANDARD HOLDING REGISTER

ASSIGNMENTS

The Holding Register address assignments for the ACS are listed in Table H-2 which follows. Unless

otherwise specified, all Holding Register Menu items are Read/Write (R/W).

Table H-2: ACS Standard Holding Register Address Mapping

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

0 (0x0000)

thru

3 (0x0003)

(Reserved)

4 (0x0004)

Net Header Set

Temp

40 to 220°F

Valid when Hdr Set

Mode=Remote Setpt

and Remote Signal =

Network

5 (0x0005)

System Start Temp 32 to 120°F

Default = 70°F

6 (0x0006)

System Start Option

0 or 1

0 = Temp Only,

1 = Temp and Load

Default = 0

7 (0x0007)

Manual Hdr Set

Temp/Internal Setpt 40 to 220°F

Default = 160°F

8 (0x0008)

Bldg Ref Temp

40 to 220°F

Default = 70°F

9 (0x0009)

Not Applicable

10 (0x000A) Not Applicable

11 (0x000B) Reset Ratio

0.3 to 3.0

(0.1 increments),

Default = 1.2

(Value x 10)

12 (0x000C) Max Header Temp 40 to 220°F

Default = 200°F

13 (0x000D) Min Header Temp

40 to 220°F

Default = 40°F

14 (0x000E) Start Percent

25 to 100%

Default = 20%

15 (0x000F) Stop Percent

10 to 45%

Default = 16%

16 (0x0010) Integral Gain

0.00 to 9.99 Rep/Min

(in 0.01 increments

Default = 0.15 Rep/Min

(Value x 100)

17 (0x0011) Header Set Mode

0, 1, or 2

0 = Constant Setpt

1 = In/Outdoor Reset

2 = Remote Setpt

Default = 0

(Constant Setpt))