Diagnostic leds – Carrier 48AJ User Manual

Page 114

Advertising
background image

114

The alarm codes for the IGC control board are shown in

Table 44.

Table 44 — IGC Control Board LED Alarms

Diagnostic LEDs —

There are 3 LEDs (red, yellow, and

green) on the lower right hand side of the control board. The

red light is used to check unit operation and alarms. A constant

pulse is normal unit operation. A series of quick blinks indi-

cates an alarm. Refer to Table 45 below for a description of

alarms. The yellow LED blinks during transmission with the

CCN (Carrier Comfort Network). The green LED blinks dur-

ing transmission with the expansion board.

Table 45 — Control Board LED Alarms

LEGEND

INDICATION

ERROR MODE

ON

Normal Operation

OFF

Hardware Failure

1 FLASH

Fan ON/OFF Delay Modified

2 FLASHES

Limit Switch Fault

3 FLASHES

Flame Sense Fault

4 FLASHES

4 Consecutive Limit Switch Faults

5 FLASHES

Ignition Lockout Fault

6 FLASHES

Induced Draft Motor Fault

7 FLASHES

Rollout Switch Fault

8 FLASHES

Internal Control Fault

9 FLASHES

Software Lockout

LED

BLINKS

ERROR

CODE

DESCRIPTION

RESET

METHOD

ACTION TAKEN

BY CONTROL

TROUBLESHOOTING COMMENTS

1

Normal Operation

None

The expansion board and control board flash the red LED
in one-second intervals when the board is operating properly.

2

HF-13

Compressor 1 Safety

Automatic

and

Manual

Cooling disabled.
Automatic reset after
15 minutes. Manual if
repeated 3 times in
90 minutes.

The high or low pressure safety switch for compressor no. 1
has opened for 3 seconds. The error will be cleared and
compressor no. 1 will be allowed to turn on in 15 minutes.
If the safeties have been tripped 3 times in 90 minutes,
compressor no. 1 will be locked out until the control
board has been manually reset.

3

HF-14

Compressor 2 Safety

Automatic

and

Manual

Cooling disabled.
Automatic reset after
15 minutes. Manual if
repeated 3 times in
90 minutes.

The high or low pressure safety switch for compressor no. 2
has opened for 3 seconds. The error will be cleared and
compressor no. 2 will be allowed to turn on in 15 minutes.
If the safeties have been tripped 3 times in 90 minutes,
compressor no. 2 will be locked out until the control
board has been manually reset.

4

HF-15

Thermostat Failure

Automatic Alarm generated.

The thermostat is calling for both heating and cooling
at the same time. The unit will operate on a first call basis
and will automatically reset.

5

HF-05

SAT Thermistor Failure

Automatic Heating, cooling, and

economizer disabled.

The supply-air temperature (SAT) sensor has failed.
First check for wiring errors, then replace sensor.

6

HF-06

OAT Thermistor Failure

Automatic NTFC, IAQ purge,

economizer, and low
ambient DX cooling
locked out disabled.

The outside air temperature (OAT) sensor has failed.
First check for wiring errors, then replace sensor.

7

HF-03

Space Temp. Sen. Failure Automatic Disables unoccupied

cooling/heating, CV
economizer, and CV
cooling/heating.

The space temperature sensor has failed.
First check for wiring errors, then replace sensor.

8

HF-12

RAT Thermistor Failure

Automatic VAV heating

disabled.

The return-air temperature (RAT) sensor has failed.
Ensure that the unit is a VAV unit. If NOT a VAV unit set
DIP switch position 1 to the closed position and reset power.
Then check for wiring errors. Finally, replace sensor.

9

SE-05

Loss of Communications

with Expansion Board

Automatic Algorithms in

expansion board are
bypassed.

Communications between the expansion board and the
control board have been interrupted. Ensure that an
expansion board is installed and wired using the
wire harness supplied with the expansion module. If an
expansion board is not used ensure that DIP switch position
3 is in the closed position, and reset power.

10

HF-16

Control Board Failure

None

Control uses default
values. (May seem
as normal operation)

Generated when hardware has failed on control board.
Replace the control board.

Analog to Digital

Conversion

None

All outputs turned off.

11

HF-17

Expansion Board Failure

None

All outputs turned off. Generated when hardware has failed on the

expansion board. Replace the expansion board.

12

SE-23

Cooling SAT Low

Limit Shutdown

Automatic Alarm generated.

CV operation. When SAT low limits are below range and
compressor shut off.

DIP