Table 7 — Electrical Data — 48AJ,AK,AW,AY Units (cont)

LEGEND

*Fuse or HACR circuit breaker per NEC.

NOTES:
1. In compliance with NEC requirements for multimotor and combi-

nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. The Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.
Use the following formula to determine
the percent of voltage imbalance.
% Voltage imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

UNIT SIZE

48AJ,AK,

AW,AY

NOMINAL

VOLTAGE

(3 PH, 60 Hz)

VOLTAGE RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

POWER

SUPPLY

No. 1

No. 2

Min

Max

RLA LRA RLA LRA Qty FLA Hp

FLA

FLA

(total)

MCA

MOCP*

035

208/230

187

253

57.1

266

57.1

266

4

5.3

(ea)

10

30.8/28.0

180.5/177.7

225/225

23.6/23.6

204.1/201.3

250/250

15

46.2/42.0

195.9/191.7

250/225

23.6/23.6

219.5/215.3

250/250

20

59.4/54.0

209.7/203.7

250/250

23.6/23.6

233.3/227.3

250/250

460

414

508

25.6

120

25.6

120

4

2.7

(ea)

10

14

82.4

100

12.6

95.0

110

15

21

89.4

110

12.6

102.0

125

20

27

95.8

110

12.6

108.4

125

575

518

632

20.5

96

20.5

96

4

2.4

(ea)

10

11

66.7

80

12.6

79.3

90

15

17

72.7

90

12.6

85.3

100

20

22

78.1

100

12.6

90.7

110

040

208/230

187

253

57.1

266

69.2

345

4

5.3

(ea)

15

46.2/42.0

211.0/206.8

250/250

23.6/23.6

234.6/230.4

300/250

20

59.4/54.0

224.2/218.8

250/250

23.6/23.6

247.8/242.4

300/300

25

74.8/68.0

241.0/232.8

300/300

23.6/23.6

264.6/256.4

300/300

460

414

508

25.6

120

28.8

173

4

2.7

(ea)

15

21

93.4

110

12.6

106.0

125

20

27

99.4

125

12.6

112.0

125

25

34

107.7

125

12.6

120.3

150

575

518

632

20.5

96

26.7

120

4

2.4

(ea)

15

17

80.5

100

12.6

93.1

110

20

22

85.5

110

12.6

98.1

110

25

27

90.6

110

12.6

103.2

125

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA — Minimum Circuit Amps
MOCP— Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.

7
457