Table 5 — Controls Options and Configurations (Non-Thermostat Applications)

LEGEND

*With DIP Switch No. 5 configured to OPEN (Occupied Heat Enabled).
NOTE: Space temperature sensor and remote start/stop switch are field-supplied.

STAGED GAS UNIT APPLICATIONS — The rooftop units

may be ordered with an optional factory-installed staged gas

control system that monitors heating operation of the rooftop

unit.

Install Supply-Air Thermistors (Staged Gas Units Only) —

Supply-air thermistors are a field-installed factory-provided

component. Three supply-air thermistors are shipped with

staged gas units and are inside the heating section. Thermistor

wires must be connected to SGC (staged gas controller) in the

heating section. See Table 6 and Fig 24. The supply-air ther-

mistors should be located in the supply duct with the following

criteria:
• downstream of the heat exchanger cells

• equally spaced as far as possible from the heat exchanger

cells

• a duct location where none of the supply air thermistors

are within sight of the heat exchanger cells

• a duct location with good mixed supply air portion of the

unit.

THERMISTORS — All units are equipped with a supply air

thermistor (SAT) located in the supply fan discharge and an

outdoor air thermistor (OAT) located in the outdoor air hood.

Variable air volume (VAV) units are supplied with a return air

thermistor (RAT) located on the return air damper support.
CONSTANT VOLUME APPLICATIONS — The units, as

shipped, are operable as stand-alone units, using either a stan-

dard (mechanical or electronic) 2-stage heat, 2-stage cool ther-

mostat, or with an electronic room sensor and a timeclock to

establish unit start and stop times.

With a standard thermostat (programmable is optional),

heating and cooling operation is set by space temperature.

With a space sensor and timeclock, the machine will operate

at default values unless they are changed using appropriate in-

put devices. The space sensor senses space temperature and

may be equipped with a timed override feature, which allows

unit operation during unoccupied periods.

The space sensors may be used in multiples of 4 or 9 to

achieve space temperature averaging. The use of a space sensor

also allows the unit to be turned on and off from a remote

signal.

Table 6 — Thermistor Designations

UNIT CONFIGURATION

DEFAULT COOLING

DEFAULT HEATING

CV or VAV Unit with SPT Sensor

Unoccupied Cooling — 90 F (32 C) (SPT)
Occupied Cooling — NA

Unoccupied Heating — 55 F (13 C) (SPT)
Occupied Heating — NA

CV Unit with SPT Sensor and Remote
Start/Stop Switch

Unoccupied Cooling — 90 F (32 C) (SPT)
Occupied Cooling — 78 F (26 C) (SPT)

Unoccupied Heating — 55 F (13 C) (SPT)
Occupied Heating — 68 F (20 C) (SPT)

VAV Unit Remote Start/Stop Switch Only

Unoccupied Cooling — 90 F (32 C)(SPT)
Occupied Cooling — 55 F (13 C) SPT)

Unoccupied Heating — 55 F (13 C) (RAT)
Occupied Heating — 68 F (20 C) (RAT)*

VAV Unit with SPT Sensor and Remote
Start/Stop Switch

Unoccupied Cooling — 90 F (32 C) (SPT)
Occupied Cooling — 55 F (13 C) (SAT)

Unoccupied Heating — 55 F (13C) (SPT)
Occupied Heating — 68 F (20 C) (RAT)*

CV

Constant Volume

NA

Not Available

RAT

Return-Air Temperature

SAT

Supply-Air Temperature

SPT

Space Temperature

VAV

Variable Air Volume

IMPORTANT: An accessory field-supplied Navigator dis-

play module is required for all staged gas control units.

THERMISTOR

PIN

CONNECTION

POINT

FUNCTION AND LOCATION

PART NO.

Thermistors

SAT 1

J8 – 1,2 (SGC)

Supply Air Thermistor (SAT) — Inserted into supply section
underneath the gas heat section (factory-provided, field-installed)

HH79NZ016

SAT 2

J8 – 3,4 (SGC)

Supply Air Thermistor (SAT) — Inserted into supply section
underneath the gas heat section (factory-provided, field-installed)

SAT 3

J8 – 5,6 (SGC)

Supply Air Thermistor (SAT) — Inserted into supply section
underneath the gas heat section (factory-provided, field-installed)