Main Burners —

For all applications, main burners are

factory set and should require no adjustment.
MAIN BURNER REMOVAL (Fig. 76)

1. Shut off (field-supplied) manual main gas valve.
2. Shut off power supply to unit.
3. Remove heating access panel.
4. Disconnect gas piping from gas valve inlet.
5. Remove wires from gas valve.
6. Remove wires from rollout switch.
7. Remove sensor wire and ignitor cable from IGC board.
8. Remove 2 screws securing manifold bracket to basepan.
9. Remove 4 screws that hold the burner support plate

flange to the vestibule plate.

10. Lift burner assembly out of unit.

11. Reverse procedure to re-install burners.

Liquid Pressure at Liquid Valve (PSIG)

CHARGING CHART

BOTH CIRCUITS

ALL OUTDOOR FANS MUST BE OPERATING

Liquid T

emperature at Liquid V

alve (deg F)

140

120

100

80

60

40

50

100

150

200

250

300

350

400

Add Charge if Above Curve

Reduce Charge if Below Curve

Fig. 73 — Cooling Charging Chart,

48EJ,EK,EW,EY054-068

Fig. 74 — Cooling Charging Chart,

48AJ,AK,AW,AY020-060

OFF

ON

W-1

W-2

D-1 D-2

C1

C2

PILOT

ADJ.

INLET PRESSURE TAP
(PLUGGED)
1/8 - 27 N.P.T. THDS.

2 LEADS, #18 WIRE 1/32 INSULATION,
600V. MAX., 105

°C

REGULATOR
ADJUSTMENT SCREW
(REMOVE COVER)

OUTLET PRESSURE
TAP (PLUGGED)
1/8-27 N.P.T. THDS.

PILOT CONNECTION
FOR 1/4” O.D. TUBING
(PLUGGED)

RECEPTACLE AND
TAB COMBINATION
TERMINAL

RECEPTACLE TERMINAL

Fig. 75 — Gas Valve (Part Number EF33CB271)

Fig. 76 — Main Burner Removal