Table 24 — Fan Performance, 48AW,AY035 — Horizontal Discharge Units

LEGEND
Bhp — Brake Horsepower
NOTES:

1. Fan performance is based on wet coils, economizer, roof curb,

cabinet losses, and clean 2-in. filters.

2. Conversion — Bhp to watts:

3. Variable Air Volume units will operate down to 70 cfm/ton. Per-

formance at 70 cfm/ton is limited to unloaded operation and
may be additionally limited by edb (entering dry bulb) and ewb
(entering wet bulb) conditions.

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

7,000

455

2.15

508

2.52

558

2.90

605

3.29

650

3.69

693

4.10

734

4.52

774

4.95

8,000

505

2.92

553

3.32

598

3.73

641

4.14

682

4.56

722

4.99

761

5.43

798

5.87

9,000

556

3.85

599

4.28

641

4.72

680

5.15

719

5.60

756

6.04

792

6.50

827

6.96

10,000

608

4.96

648

5.42

686

5.87

723

6.34

758

6.81

793

7.28

826

7.75

859

8.24

11,000

661

6.26

698

6.74

733

7.22

767

7.71

800

8.20

832

8.70

864

9.19

895

9.70

12,000

715

7.76

749

8.25

781

8.76

813

9.27

844

9.79

874

10.31

904

10.83

933

11.35

13,000

769

9.46

800

9.98

831

10.51

861

11.05

890

11.59

918

12.13

946

12.67

974

13.22

14,000

824

11.39

853

11.92

881

12.48

909

13.03

937

13.60

964

14.16

990

14.73

1016

15.30

15,000

879

13.54

906

14.10

933

14.67

959

15.25

985

15.84

1010

16.42

1035

17.01

1060

17.60

16,000

934

15.94

959

16.52

984

17.11

1009

17.70

1034

18.31

1058

18.92

1082

19.53

1105

20.14

17,000

989

18.58

1013

19.18

1037

19.79

1060

20.41

1084

21.03

1107

21.66

1129

22.29

1151

22.92

18,000

1044

21.49

1067

22.10

1090

22.73

1112

23.37

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.8

2.0

2.2

2.4

2.6

2.8

3.0

3.2

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

7,000

811

5.39

847

5.83

882

6.29

915

6.75

947

7.21

977

7.68

1007

8.15

1035

8.63

8,000

834

6.33

869

6.79

902

7.26

935

7.74

966

8.22

997

8.71

1026

9.21

1055

9.71

9,000

861

7.44

894

7.92

926

8.40

957

8.90

988

9.40

1017

9.90

1046

10.42

1075

10.94

10,000

891

8.73

922

9.22

953

9.72

983

10.23

1012

10.75

1041

11.27

1069

11.80

1096

12.33

11,000

925

10.20

954

10.72

983

11.24

1012

11.76

1040

12.29

1067

12.83

1094

13.37

1120

13.92

12,000

961

11.88

989

12.41

1017

12.95

1044

13.49

1070

14.04

1096

14.59

1122

15.15

1147

15.71

13,000

1000

13.76

1027

14.32

1053

14.87

1078

15.43

1104

16.00

1129

16.57

1153

17.14

1177

17.72

14,000

1041

15.86

1066

16.44

1091

17.01

1116

17.59

1140

18.18

1163

18.76

1187

19.35

15,000

1084

18.19

1108

18.79

1131

19.38

1155

19.98

1178

20.58

16,000

1128

20.75

1151

21.37

1173

21.98

1196

22.60

17,000

18,000

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

3.4

3.6

3.8

4.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

7,000

1063

9.11

1090

9.60

1115

10.09

1141

10.58

8,000

1082

10.21

1109

10.72

1135

11.23

1161

11.75

9,000

1102

11.46

1129

11.99

1155

12.52

1180

13.05

10,000

1123

12.87

1149

13.42

1175

13.97

1200

14.52

11,000

1146

14.47

1172

15.03

1197

15.60

12,000

1172

16.28

1197

16.85

13,000

14,000

15,000

16,000

17,000

18,000

Watts =

Bhp x 746