Carrier 48AJ User Manual

Page 47

Advertising
background image

47

Conductors and drain wire must be 20 AWG minimum

stranded, tinned copper. Individual conductors must be insulat-

ed with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An

aluminum/polyester 100% foil shield and an outer jacket of

PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum op-

erating temperature range of -20 C to 60 C (-4 F to 140 F) is re-

quired. Table 9 lists cables that meet the requirements.

Table 9 — CCN Connection Approved

Shielded Cables

Table 10 — Color Code Recommendations

NOTE: If a cable with a different color scheme is selected, a

similar color code should be adopted for the entire network.

At each system element, the shields of the communication

bus cables must be tied together. If the communication bus is

entirely within one building, the resulting continuous shield

must be connected to a ground at one point only. If the com-

munication bus cable exits from one building and enters anoth-

er, the shields must be connected to grounds at the lightning

suppressor in each building where the cable enters or exits the

building (one point per building only).

To connect the unit to the network:

1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white

(ground), and black (-) conductors. (If a different network

color scheme is used, substitute appropriate colors.)

3. Remove the 3-pin male plug from the base control board

in the main control box, and connect the wires as follows:

a. Insert and secure the red (+) wire to terminal 1 of

the 3-pin plug.

b. Insert and secure the white (ground) wire to termi-

nal 2 of the 3-pin plug.

c. Insert and secure the black (-) wire to terminal 3 of

the 3-pin plug.

4. Insert the plug into the existing 3-pin mating connector

on the base module in the main control box.

MANUFACTURER

CABLE PART NO.

Alpha

2413 or 5463

American

A22503

Belden

8772

Columbia

02525

IMPORTANT: When connecting the CCN communica-

tion bus to a system element, use a color coding system for

the entire network to simplify installation and checkout.

See Table 10.

SIGNAL

TYPE

CCN BUS CONDUCTOR

INSULATION COLOR

CCN PLUG

PIN NO.

Positive (+)

RED

1

Ground

WHITE

2

Negative (-)

BLACK

3

Fig. 32 — Field Control Thermostat Wiring

NOTE: Sensor part numbers are as follows:

T-55 — CEC0121448-01
T-56 — CEC0121448-01

Fig. 33 — Field Control Temperature Sensor

Wiring (CV or VAV Units)

Advertising
This manual is related to the following products: