The Time Guard® function maintains a minimum off

time of 5 minutes, a minimum ON time of 10 seconds, and a

minimum delay before starting the second compressor of

10 seconds.

If the compressors have been off for more than 15 minutes

and the OAT (outdoor-air temperature) is less than 45 F, then

the safeties will be ignored for 5 minutes. At all times, safeties

will be used.

Heating and cooling will be mutually locked out on demand

on a first call basis. The heating and the cooling functions can-

not be operating simultaneously.
COOLING, VARIABLE AIR VOLUME (VAV) UNITS —

On power up, the control module will activate the initialization

software of the control board. The initialization software then

reads DIP switch no. 1 position to determine CV or VAV oper-

ation. Initialization clears all alarms and alerts, re-maps the in-

put/output database for VAV operation, sets maximum heat

stages to 1 and sets maximum cool stages to 6. The control

module reads DIP switch no. 3 and determines if the unit will

use expansion board operation. Power up takes a random time

of 1 to 63 seconds plus 5 minutes the first time power is sent to

the control board after a power outage.

The control module will determine if an interface (linkage)

is active and if the unit will operate in a Digital Air Volume

(DAV) mode. In a DAV system, the room terminals are

equipped with microprocessor controls that give commands to

the base unit module. If an interface is active, the control will

replace local comfort set points, space and return air tempera-

tures and occupancy status with the linkage data supplied.

The control module will determine occupancy status from

Time Schedules (if programmed), Remote Occupied/Unoccu-

pied input, global occupancy, or DAV. If Temperature Com-

pensated Start is active, the unit will be controlled as in the

Occupied mode.
NOTE: The temperature compensated start is a period of time

calculated to bring the unit on while in Unoccupied mode to

reach the occupied set point when occupancy occurs.

The control module will set the appropriate operating mode

and fan control. The control module will turn VFD on if Occu-

pied mode is evident.

For units equipped with a start/stop switch only (no space

temperature sensor), if in Unoccupied mode and valid return-

air temperature reading is available (either from a sensor or

DAV), the control will monitor return-air temperature against

Unoccupied Heat and Cool set points.

For units with a start/stop switch and a space temperature

sensor, the control module will start the VFD whenever SPT is

outside of the set points (Unoccupied Heat or Unoccupied

Cool). The VFD may also be started by nighttime thermostat

via remote Occupied/Unoccupied input or by a Temperature

Compensated Start algorithm. When VFD is running in a nor-

mal mode, the control will start heating or cooling as required

to maintain supply-air temperature at the supply air set point

(SASP) plus the reset (when enabled). The reset value is deter-

mined by SAT (supply-air temperature) reset and/or space tem-

perature reset algorithms. The space temperature reset is only

available when enabled through software.

When cooling, the control will energize the power exhaust

enable output to the external power exhaust controller, when

power exhaust is used.

If in Occupied mode, the control module will perform econ-

omizer control (economizer control same as described above

for CV units). If in Unoccupied mode, the control module will

perform nighttime free cool and IAQ pre-occupancy purge as

required (when enabled through software). When DX (direct

expansion) cooling is called, the outdoor fans will always

operate.

The control will run continuous diagnostics for alarms/

alerts; respond to CCN communications and perform any con-

figured network POC (product outboard controls) functions

such as time and outdoor-air temperature broadcast and global

broadcast; and perform Fire/Smoke control if equipped with

power exhaust.
GAS HEATING, CONSTANT VOLUME (CV) UNITS —

The gas heat units incorporate 2 (48AJ,AK,AW,AY020-050

and 48EJ,EK,EW,EY024-048) or 3 (48AJ,AK,AW,AY060 and

48EJ,EK,EW,EY054-068) separate systems to provide gas

heat. Each system incorporates its own induced-draft motor, In-

tegrated Gas Control (IGC) board, 2 stage gas valve, manifold,

etc. The systems are operated in parallel; for example, when

there is a call for first stage heat, all induced-draft motors oper-

ate, all gas valves are energized, and both IGC boards initiate

spark.

All of the gas heating control is performed through the IGC

boards (located in the heating section). The control module

board serves only to initiate and terminate heating operation.

The control module board is powered by 24 vac. When the

thermostat or room sensor calls for heating, power is sent from

the control module board to W on each of the IGC boards. An

LED on the IGC board will be on during normal operation. A

check is made to ensure that the rollout switches and limit

switches are closed and the induced-draft motors are not run-

ning. The induced-draft motors are then energized, and when

speed is proven with the hall effect sensor on the motor, the

ignition activation period begins. The burners will ignite within

5 seconds.

When ignition occurs the IGC board will continue to moni-

tor the condition of the rollout and limit switches, the hall effect

sensor, as well as the flame sensor. If the unit is controlled

through a room thermostat set for fan auto., 45 seconds after

ignition occurs, the indoor-fan motor will be energized and the

outdoor-air dampers will open to their minimum position. If for

some reason the overtemperature limit opens prior to the start

of the indoor fan blower, on the next attempt, the 45-second de-

lay will be shortened to 5 seconds less than the time from initi-

ation of heat to when the limit tripped. Gas will not be inter-

rupted to the burners and heating will continue. Once modified,

the fan on delay will not change back to 45 seconds unless

power is reset to the control. If the unit is controlled through a

room sensor, the indoor fan will be operating in the Occupied

mode and the outdoor-air dampers will be in the minimum

position.

If the unit is controlled with a room sensor in the Unoccu-

pied mode, the indoor fan will be energized through the IGC

board with a 45-second delay and the outside-air dampers will

move to the IAQ position (generally set to zero in the Unoccu-

pied mode). The IAQ feature is enabled through system soft-

ware. If IAQ is not enabled, dampers will move to the mini-

mum position.

When additional heat is required, W2 closes and initiates

power to the second stage of the main gas valves. When the

thermostat is satisfied, W1 and W2 open and the gas valves

close interrupting the flow of gas to the main burners. If the call

for W1 lasted less than 1 minute, the heating cycle will not ter-

minate until 1 minute after W1 became active. If the unit is

controlled through a room thermostat set for fan auto., the

indoor-fan motor will continue to operate for an additional

45 seconds then stop and the outdoor-air dampers will close. If

the overtemperature limit opens after the indoor motor is

stopped within 10 minutes of W1 becoming inactive, on the

next cycle the time will be extended by 15 seconds. The maxi-

mum delay is 3 minutes. Once modified, the fan off delay will

not change back to 45 seconds unless power is reset to the con-

trol. If the unit is controlled through a room sensor, the indoor

fan will be operating in the Occupied mode and turned off after

45 seconds in the Unoccupied mode.