Features with Thermostat Control of Unit
• two-stage heating

• two-stage cooling

• control of unit using Y1, Y2, W1, W2, and G thermostat

inputs

• control of the indoor fan

• outdoor-air temperature/supply-air temperature

monitoring

• control of an outdoor air condenser fan based on out-

door-air temperature

• control of modulating economizer damper to provide

free cooling when outdoor conditions are suitable, using

supply-air temperature as a control point

• control of the economizer damper and indoor fan to

obtain unoccupied free cooling

• provide power exhaust output to an external power

exhaust controller

• support a field test for field checkout

• control of 2 stages of CV power exhaust

• compressor Time Guard® (power up, minimum off and

on times)

• compressor lockout during low supply-air temperature

Additional features are provided by accessing the standard

unit control board via software with a computer. These features

are:
• electronic expansion board features (if installed)

• control board diagnostics

• ability to change supply air set point (economizer control)

• ability to change high outdoor temperature lockout set

point (economizer control)

• ability to change power exhaust set points

NOTE: A CV unit without a thermostat requires a field-

supplied sensor for operation.
Features with Sensor Control of Unit (Stand-Alone Applica-

tions — Unit control is limited to CV unoccupied default set

points, 90 F for cooling, 55 F for heating unless a computer has

been used to change the set points. There are 2 sensor options

available:
• T-55 sensor will monitor room temperature and provide

unoccupied override capability (1 hour)

• T-56 sensor will monitor room temperature, provide

unoccupied override capability (1 hour), and provide a

temperature offset of 5° F.

Standard features are:

• support of remote occupied/unoccupied input to start and

stop the unit

• cooling capacity control of 3 stages using economizer

and 2 compressors to maintain space temperature to an

occupied or unoccupied set point

• enable heating or cooling during unoccupied periods as

required to maintain space temperature within the unoc-

cupied set points

• adjustment of space temperature set points of ±5° F when

using a T-56 sensor

• provides CCN (Carrier Comfort Network) IAQ (Indoor-

Air Quality) participation

• control of modulating economizer damper to maintain

indoor air quality (IAQ) when outdoor conditions are

suitable (this function is provided in the base unit con-

trols on units with serial number 0600F or later)

NOTE: The IAQ sensor must be set for current output (4 to

20 mA), not voltage output. Ensure the jumper on the sensor is

in the upper position. See Fig. 25.

Additional features with sensor control of unit (with com-

puter access or Remote Enhanced Display) are:
• 365-day timeclock with backup (supports minute, hour,

day of week, date, month, and year)

• daylight savings time function

• occupancy control with 8 periods for unit operation

• holiday table containing up to 18 holiday schedules

• ability to initiate timed override from T-55 or T-56 sen-

sors for a timed period of 1 to 4 hours

• ability to use multiple space temperature sensors to aver-

age the space temperature

• supply-air temperature reset for the supply-air tempera-

ture set point

• temperature compensated start to calculate early start

times before occupancy

• access to the Display, Maintenance, Configuration, Ser-

vice, and Set Point data tables through network software

• loadshed and demand limiting

When the unit is equipped with a field-supplied space tem-

perature sensor and a remote contact closure (remote start/

stop) on the base control board, the occupied default set points

will monitor unit operation. The occupied default set points are

78 F cooling and 68 F heating (if heating is present). See

Fig. 26 for remote start/stop wiring.
NOTE: For units with a field-supplied space temperature sen-

sor which have not had the base unit control board accessed

via software to set an occupancy schedule, the remote start/

stop closure will allow the unit to operate in the pre-configured

occupied default set points of 78 F cooling and 68 F heating.

Without this feature, the unit will control to the unoccupied

default set points of 90 F cooling and 55 F heating.

Fig. 24 — Supply-Air Thermistor Connections