Minimum Damper Position (MDP) Setting — Setting of the

outdoor air damper position is performed in conjunction with a

shortened version of the field run test. This is performed by

first opening DIP (Dual In-line Package) switch no. 4 then

no. 6. See Fig. 27 and Direct Digital Controls DIP Switch Con-

figuration section on page 63.

The outdoor-air damper closes. The control allows 90 sec-

onds for the damper to close in case it is in the full open

position. Next, the indoor-fan contactor will energize. The

outdoor-air damper will remain at 0% for 30 seconds. It will

then move to the 10% damper motor travel position for another

30 seconds. This will be repeated at every 10% increment for

30 seconds until the damper reaches 100% open. Close DIP

switch no. 4 during the 30 seconds immediately after the de-

sired outdoor air minimum damper position. The 30-second

time period is to allow time where DIP switch no. 4 can be

closed. The default value of the minimum outdoor air damper

position is 20%. If the desired minimum position is 30%, al-

lows the damper position to go to 10% for 30 seconds, then

20% for 30 seconds, and when it reaches 30% close DIP switch

no. 4 during the 30-second period following the 30% position.

The minimum outdoor air damper position is now set. Close

DIP switch no. 6.

HOOD SIDE

MOUNTING
FLANGE

HOOD TOP

HOOD SIDE

CROSS MEMBER

GRAY FOAM STRIP

Fig. 38 — Adding Seal Strip to Sides of Hood Top

Mounting Flange

Fig. 39 — Adding Seal Strip to Back of Hood Top

Mounting Flange

Fig. 40 — Adding Foam Strip to Cross Member

HOOD SIDE
(SLOTTED)

HOOD
TOP

Fig. 41 — Adding Foam Strip to Hood Side

BLOCKOFF BAFFLE

GRAY FOAM STRIP

Fig. 42 — Adding Seal Strip to

Blockoff Baffle