Step 5 — Install Flue Hood

48AJ,AK,AW,AY020-050 AND 48EJ,EK,EW,EY024-048

UNITS — Flue hood is shipped inside gas section of unit. To

install, secure flue hood to access panel. See Fig. 20A.
48AJ,AK,AW,AY060 AND 48EJ,EK,EW,EY054-068

UNITS — Flue hood and wind baffle are shipped inside gas

section of unit. To install, secure flue hood to access panel. In-

stall the two pieces of the wind baffle over the flue hood. See

Fig. 20B.
NOTE: When properly installed, flue hood will line up with

combustion fan housing. See Fig. 21.

Step 6 — Trap Condensate Drain —

See Fig. 5-16

for drain location. Condensate drain is open to atmosphere and

must be trapped. Install a trapped drain at the drain location.

One 1-in. FPT coupling is provided inside the unit evaporator

section for condensate drain connection. A trap at least 4-in.

deep must be used. See Fig. 22. Trap must be installed to pre-

vent freeze-up.

Condensate pans are sloped so that water will completely

drain from the condensate pan to comply with indoor air quali-

ty guidelines. The condensate drain pans are not insulated.

Step 7 — Install Gas Piping —

Unit is equipped for

use with natural gas. Installation must conform with local

building codes or, in the absence of local codes, with the Na-

tional Fuel Gas Code, ANSI Z223.1.

Install manual gas shutoff valve with a

1

/

8

-in. NPT pressure

tap for test gage connection at unit. Field gas piping must in-

clude sediment trap and union. See Fig. 23. An

1

/

8

-in. NPT is

also located on the gas manifold adjacent to the gas valve.

Do not pressure test gas supply while connected to unit.

Always disconnect union before servicing.

FLUE HOOD

GAS SECTION
ACCESS PANEL

WIND
BAFFLE

TOP VIEW

SIDE VIEW

Fig. 20A — Flue Hood Location

(48AJ,AK,AW,AY020-050 and

48EJ,EK,EW,EY024-048 Units)

Fig. 20B — Flue Hood Location

(48AJ,AK,AW,AY060 and

48EJ,EK,EW,EY054-068 Units)

Fig. 21 — Combustion Fan Housing Location

Fig. 22 — Condensate Drain Trap Piping Details