Install Motormaster® III Controls — Only one Motormaster

III control is required per unit.
Motor — One outdoor-fan motor (OFM) must be changed out

in the field to accommodate the Motormaster III accessory.

The replacement motor part no. is HD52AK652.

For 48AJ,AK,AW,AY020-030 and 48EJ,EK,EW,EY024-

034 units, the Motormaster controlled OFM is the no. 2 OFM

and is located at the left side of the unit looking from the com-

pressor end. The no. 1 OFM is controlled to shut off at 55 F and

on at 65 F outdoor-air temperature and does NOT need to be

changed out.

For 48AJ,AK,AW,AY035-050 and 48EJ,EK,EW,EY038-

054 units, the Motormaster controlled OFM is no. 1 OFM and

is located at the left side of the unit looking from the compres-

sor end and the second motor back. The no. 3 and 4 OFM are

controlled to shut off at 55 F and on at 65 F outdoor-air temper-

ature and do NOT need to be changed out. The no. 2 OFM is

intended to run at all ambient temperatures.

For 48AJ,AK,AW,AY060 and 48EJ,EK,EW,EY058-068

units, the Motormaster controlled OFM is no. 3 OFM and is lo-

cated at the left side of the unit looking from the compressor

end and the second motor back.

The no. 4, 5, and 6 OFMs are controlled to shut off at 55 F

and on at 65 F outdoor-air temperature and do NOT need to be

changed out. The no. 1 and 2 OFMs are intended to run at all

ambient temperatures.
Sensor — Install the sensor for thermistor input control in the

location shown in Fig. 53A-53E. Connect sensor leads to the

violet and gray control signal leads on the Motormaster III

control.
Signal Selection Switch — Remove the cover of the Motor-

master III control. Set the switch to accept the thermistor

sensor input signal. Set the frequency to match the unit power

supply (60 Hz).
Motormaster III Control — The recommended mounting loca-

tion is in the indoor fan section, mounted on the panel that sep-

arates the indoor and outdoor sections. On VAV units, this

location is next to the VFD (variable frequency drive).

Do not route the Motormaster III control wiring next to the

VFD on VAV units. Use a separate connector through the parti-

tion when wiring to the OFM.
Electrical Connections

When replacing the OFM, reconnect the black, yellow, and

blue wires form the outdoor fan contactor to the black, yellow,

and blue wires of the Motormaster III control. Run new wires

from the red, orange, and brown wires to the leads of the new

OFM. Connect the green wire from the control to ground.
NOTE: On all 575-v units, 2 transformers (part no.

HT01AH851) must be used for each Motormaster III control

to lower the supply voltage to the control to 460-v. Transform-

ers can be mounted anywhere outside the control box.

To avoid possibility of electrical shock and personal

injury, turn off all power to unit before making electrical

connections.

18

1

BOTH SIDES

CROSS-BREAK

0.5

61

4.62

17.167
BETWEEN
HOLES
(TYPICAL)

0.312 DIA
HOLES

B

A

NOTE: All dimensions are in inches. Material: 20 gage galvanized
steel or other non-corrosive material.

Fig. 52 — Motormaster III Control Baffle Details

UNIT SIZE

A

B

48AJ,AK,AW,AY020-050 and

48EJ,EK,EW,EY024-054

80.5

79.5

48AJ,AK,AW,AY060 and

48EJ,EK,EW,EY058-068

120.5

119.5

Fig. 53A — Motormaster III Sensor Location

(48AJ,AK,AW,AY020-030 and

48EJ,EK,EW,EY024-034)