Carrier 48AJ User Manual

Page 54

Advertising
background image

54

Step 12 — Install All Accessories —

After all the

factory-installed options have been adjusted, install all field-in-

stalled accessories. Refer to the accessory installation instruc-

tions included with each accessory.
MOTORMASTER® III CONTROL INSTALLATION
Install Field-Fabricated Wind Baffles — Wind baffles must

be field-fabricated for all units to ensure proper cooling cycle

operation at low-ambient temperatures. See Fig. 52 for baffle

details. Use 20-gage, galvanized sheet metal, or similar corro-

sion-resistant metal for baffles. Use field-supplied screws to at-

tach baffles to unit. Screws should be

1/4

-in. diameter and

5/8

-in.

long. Holes for wind baffles are pre-punched in the unit sheet

metal.

The wind baffles attach to flanges formed on the outer sheet

metal of the unit corner post. The other end of the baffle is at-

tached to the center panel between the condenser coil and the

indoor section. Two baffles are required.

To avoid damage to the refrigerant coils and electrical com-

ponents, use recommended screw sizes only.

NOTES:

1. Unless otherwise specified, all dimensions are to outside of part.
2. Dimensions are in inches.
3. On 48AW,AY and 48EW,EY units, accessory barometric relief or power exhaust must be mounted in the field-supplied return ductwork.

Fig. 50 — Barometric Relief Damper and Power Exhaust Mounting Details

LEGEND
VAV — Variable Air Volume

Fig. 51 — Pressure Transducer Locations

(48AJ,AK,AW,AY060 and 48EJ,EK,EW,EY054-068)

Advertising
This manual is related to the following products: