Size gas-supply piping for 0.5-in. wg maximum pressure

drop. Do not use supply pipe smaller than unit gas connection.

OPTIONAL STAGED GAS UNITS — The staging pattern

is selected based on Heat Stage Type (HTSTGTYP). Max

Capacity per changes default value is selected based on Capac-

ity Maximum Stage (CAPMXSTG). See Table 4.

For complete information and service instructions for

Staged Gas Control Units, see Control Operation and Trouble-

shooting literature.

Step 8 — Controls Options —

The control options

that the units can provide are based on the following parame-

ters: CV (constant volume) or VAV (variable air volume) oper-

ation; stand-alone unit with field-supplied sensors installed

(CV or VAV); as a system via Carrier Comfort System (TEMP

or VVT® [Variable Volume and Temperature]); optional elec-

tronic expansion board installed (CV or VAV); linked to the

Carrier Comfort Network; availability of a computer and soft-

ware (ComfortWORKS® Building Supervisor, and Service

Tool) or remote enhanced display accessory installed to access

the base control board; and optional factory-installed staged

gas control. See Table 5.
NOTE: Access to the base control board allows unit occu-

pancy schedules, unit timeclock, and various set points to be

changed from their factory-defined default settings.

Table 4 — 48A,E Series Staged Gas Implementation

IMPORTANT: Natural gas pressure at unit gas connection

must not be less than 5 in. wg or greater than 13.5 in. wg.

NUMBER OF STAGES

MODEL NUMBER POSITION

POSITION

HEAT SIZE

3

5

6,7,8

HTSTGTYP

CAPMXSTG

5 stages

E

S

024
028
030
034
038
044
048

Default=1

Default=20

Low

A

S

020
025
027
030
035
040
050

Default=1

Default=20

Low

E

T

038
044
048

Default=1

Default=20

High

A

T

035
040
050

Default=1

Default=20

High

7 stages

E

T

024
028
030
034

Default=2

Default=15

High

A

T

020
025
027
030

Default=2

Default=15

High

9 stages

E

T

054
058
064
068

Default=3

Default=15

High

A

T

060

Default=3

Default=15

High

11 stages

E

S

054
058
064
068

Default=4

Default=15

Low

A

S

060

Default=4

Default=15

Low

Fig. 23 — Field Gas Piping