Carrier 48AJ User Manual

Page 79

Advertising
background image

79

Table 33 — Motor Limitations

LEGEND
Bhp — Brake Horsepower
NOTES:

1. Extensive motor and electrical testing on the Carrier units has

ensured that the full horsepower range of the motor can be
utilized with confidence. Using your fan motors up to the

horsepower ratings shown in the Motor Limitations table will not
result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected.

2. All motors comply with Energy Policy Act (EPACT) Standards

effective October 24, 1997.

Table 34 — Air Quality Limits

LEGEND

NOTE: Variable Air Volume units will operate down to 70 cfm/ton in
Cooling mode. Performance at 70 cfm/ton is limited to unloaded
operation and may be additionally limited to edb and ewb conditions.

STANDARD EFFICIENCY MOTORS

Nominal Bhp

Maximum Bhp

Maximum Amps

Maximum

Watts

Maximum

Efficiency

230 v

460 v

575 v

5

5.9

14.6

7.9

6.0

5,030

87.5

7.5

8.7

22.0

7,717

84.1

9.5

12.0

10.0

8,008

88.5

10

10.2

28.0

8,502

89.5

11.8

14.6

12.0

9,836

89.5

15

15.3

43.8

12,543

91.0

18.0

21.9

19.0

14,756

91.0

20

22.4

62.0

18,363

91.0

23.4

28.7

23.0

19,183

91.0

25

28.9

72.0

23,511

91.7

29.4

37.4

31.0

23,918

91.7

30

35.6

95.0

28,742

92.4

34.7

48.0

47.0

28,015

92.4

40

42.0

110.0

55.0

48.8

33,690

93.0

HIGH EFFICIENCY MOTORS

Nominal Bhp

Maximum Bhp

Maximum Amps

Maximum

Watts

Maximum

Efficiency

230 v

460 v

5

5.9

15.8

7.9

4,918

89.5

7.5

8.7

22.0

7,078

91.7

9.5

12.0

7,728

91.7

10

10.2

28.0

8,298

91.7

11.8

15.0

9,600

91.7

15

15.3

43.8

12,273

93.0

18.0

21.9

14,439

93.0

20

22.4

58.2

17,853

93.6

23.4

28.7

18,650

93.6

25

28.9

73.0

23,034

93.6

29.4

36.3

23,432

93.6

30

35.6

82.6

28,374

93.6

34.7

41.7

27,656

93.6

40

42.0

110.0

55.0

33,156

94.5

UNIT

48AJ,AK,AW,A

Y

UNIT

48EJ,EK,EW,EY

MINIMUM HEATING

AIRFLOW

(Low Heat)

MINIMUM HEATING

AIRFLOW

(High Heat)

MINIMUM COOLING

AIRFLOW (VAV)

AT FULL LOAD OPERATION

MINIMUM COOLING

AIRFLOW

(CV

MAXIMUM

AIRFLOW

020

024

5,900

6,100

4,000

6,000

10,000

025

028

5,900

6,100

5,000

7,500

12,500

027

030

5,900

6,100

5,400

8,100

13,500

030

034

5,900

6,100

6,000

9,000

15,000

035

038

7,600

10,100

7,000

10,500

17,500

040

044

7,600

10,100

8,000

12,000

20,000

048

7,600

10,100

9,000

13,500

22,500

050

7,600

10,100

10,000

15,000

22,500

054

11,000

14,700

10,000

15,000

25,000

058

11,000

14,700

11,000

16,500

27,000

060

064

11,000

14,700

12,000

18,000

27,000

068

11,000

14,700

13,000

19,500

27,000

CV

Constant Volume

edb

Entering Dry Bulb

ewb — Entering Wet Bulb
VAV — Variable Air Volume

Advertising
This manual is related to the following products: